ZCS Single Phase Capacitor Switch

Notes

The Zhiyue’s new generation ZCS capacitor switch is a special electrical field design on vacuum interrupter and switch body insulation for switching capacitive current.

Detailed introduction

OVERVIEW

The Zhiyue’s new generation ZCS capacitor switch is a special electrical field design on vacuum interrupter and switch body insulation for switching capacitive current. integrated with single or three phase pole mounted capacitor bank to be reactive power compensation.

With long mechanical and electrical life design can provides an operational life of over 100,000 maintenance-free operations.  

Using the ZCS will result in substantial savings from reduced maintenance and maximized bank uptime and will also improve Power Quality.

The ZCS all comply with relative standard ANSI C37.66/IEC62271  

 

Core features

  • DURABLE

Harsh coastal environment application

  • RELIABLE

Field-proven design

  • ECONOMICAL

Vacuum insulation with low-cost oil option

 

Service condition

Ambient temperature:-40℃~+85℃, day temperature difference:25℃;

Altitude: Below 2000m(special condition pls contact ZhiyueTechnical);

Wind speed no exceeds 35m/s;

No normally intensity vibration;  

No intensity erosion gas, medium place (for example acid, alkali, smother eg.) Pollution class: IV class;

Charge temperature -40℃~+85℃

 

Technical Data

N.O.

Technical parameter

Unit

Value

1

Rated voltage

kV

15

2

Rated frequency

Hz

50/60

3

Rated current

A

630A

4

Short-time (1min) power frequency withstand voltage

kV

45

5

Lightning impulse withstand voltage (peak)

kV

95

6

Rated short-circuit breaking current

kA

20

7

Rated short-time withstand current (4S)

kA

20

8

Rated peak withstand current

kA

50

9

Rated short-circuit closing current

kA

50

10

Rated back-to-back capacitor breaking current  

A

400

11

Maximum number of short circuit breaks

times

25

12

Electrical life

times

≥10000

13

Mechanical life

times

≥10000

14

Maximum allowable wear of contacts

mm

3

15

Contact closure bounce time

ms

≤2

16

Operation difference

ms

≤2

17

Closing time

ms

≤30

18

Opening time

ms

≤30

19

Arc burning time

ms

≤15

20

Main loop resistance

μΩ

≤80

21

Rated sequence of operations

O-0.5S-CO-180S-CO

Mechanism

1

Number of closing coil

Pcs

1

2

Number of opening coil

Pcs

1

3

Rated power of motor

W

40

Auxiliary switch

1

Rated voltage

V

380

2

Rated current

A

10

3

Number of contact

Pcs

4NC&4NO

 

Message Feedback

If you have any enquiry about quotation or cooperation,please free to email us at niki@zhiyue.com or use the following enquiry form,Our sales representative will contact you within 24 hous.thank you for your interest in our products.

News Center

Overview of high-voltage load switches, functions, precautions, environmental conditions, and application areas

What is high voltage disconnect switch?

Principles for the use of high-voltage isolation switches and circuit breakers

how to install high voltage power capacitor

Can't find what you're looking for?
In the past 32 years, Zhiyue Group Co., Ltd. has been helping many well-known companies and organizations to provide high-voltage power capacitors, low-voltage capacitors, vacuum contactors, vacuum circuit breakers, high-voltage load switches, high-voltage disconnect switch, high voltage transformer.
Contact Our Experts
Message
Cell Phones Telephone E-mail

Back To Top

Leave Message Here!
GET IN TOUCH NOW
×