ZN63(VBM7)-12 fixed indoor vacuum circuit breaker

Notes

VS1-12 side-mounted type vacuum circuit breaker is a kind of indoor high voltage switch device which is used in the AC Three-phase power system of frequency 50HZ,rated voltage 12KV to be the protection and control unit. 
Because of the special superiority of vacuum circuit breaker, especially suitable for applications that require frequent operation at rated operating Current or multiple open short-circuit breaking current location.

Detailed introduction

ZN63(VBM7)-12 fixed indoor vacuum circuit breaker

ZN63(VBM7)-12 Indoor High Voltage Vacuum Circuit Breaker

Summary
VS1-12 side-mounted type vacuum circuit breaker is a kind of indoor high voltage switch device which is used in the AC Three-phase power system of frequency 50HZ,rated voltage 12KV to be the protection and control unit. Because of the special superiority of vacuum circuit breaker, especially suitable for applications that require frequent operation at rated operating Current or multiple open short-circuit breaking current location. It 1s especially suitable to the place requiring frequent operations.
VS1-12 side-mounted type vacuum circuit breaker adopts fixed installation, which is mainly used in the fixed switchgear. It can be used alone or used in ring network power supply system, box-type variable system and non-standard power supply system to protect and control the

Technical Specifications

NO. Item Units Parameters
1 Rated voltage kV 12
2 Rated cu rrent A 630~1250 1250 1250
3 Rated short-circu it breaking cu rrent kA 20 25 31.5
4 Rated short-circu it closing cu rrent kA 50 63 80
5 Rated peak withstand cu rrent kA 50 63 80
6 4S rated short-ci rcu it withstand current kA 20 25 31.5
7 Rated
insulation level
1min power freq uency voltage kV 42 (fracture 48)
Lightning Impulse Withstand voltage (peak) 75 (fracture 65)
8 Rated operat i ng sequence   O- 0.3S-CO-180S-CO
9 Mechanism life Times 10000
10 Opening times of rated short-circuit breaking current Times 50
11 Rated operator closing voltage(DC) V AC/DC  220,110
12 Rated operator open i ng voltage(DC) V AC/DC  220,110
13 Clearance between open contact mm 11 ± 1
14 Over-travel( Contact springcompression degree) mm 3.5 ± 0.5
15 Three phase points, closing bounce time ms ≤2
16 Contact closing bounce time ms ≤2
17 Average opening speed m/s 1.1 ± 0.2
18 Average closing speed m/s 0.6 ± 0.2
19 Operning
 time
The highest operati n g voltage s ≤0.05
The lowest operating voltage ≤0.08
20 Closing time s 0.1
21 Dynamic and static contact allowed to weara cumulative thickness mm 3

Model Implication

Overall Dimensions

 

Message Feedback

If you have any enquiry about quotation or cooperation,please free to email us at niki@zhiyue.com or use the following enquiry form,Our sales representative will contact you within 24 hous.thank you for your interest in our products.

News Center

Overview of high-voltage load switches, functions, precautions, environmental conditions, and application areas

What is high voltage disconnect switch?

Principles for the use of high-voltage isolation switches and circuit breakers

how to install high voltage power capacitor

Can't find what you're looking for?
In the past 32 years, Zhiyue Group Co., Ltd. has been helping many well-known companies and organizations to provide high-voltage power capacitors, low-voltage capacitors, vacuum contactors, vacuum circuit breakers, high-voltage load switches, high-voltage disconnect switch, high voltage transformer.
Contact Our Experts
Message
Cell Phones Telephone E-mail

Back To Top

Leave Message Here!
GET IN TOUCH NOW
×