XD1 current-limiting reactor

Notes

1.Rated current, capacity and surge-limiting times of mated capacitor.
2.Power frequency testing voltage: AC 50Hz, voltage 3Kv, no break-down or flash for 1min.
3.Temperature: Housing<=65K, Coil<=65K.

Detailed introduction

current-limiting reactor

XD1 current-limiting reactor

General Description:
XD1 series current-limiting reactor adopts dry type reactor cast by uns-aturated polyesters resin. It is used to control the switch-on surge of low-voltage capacitor and to strength the breaking capability of switch-on switch in the low-voltage electric engineering integrated device.

Working condition:
1.Altitude of installing place not higher than 1000m
2.When ambient air temperature is lower than +40℃, the average temperature within 24h should lower than +35℃, the lower limit of ambient air temperature is -5℃。
3.When max temperature is +40℃, the air relative humidity doesn’t exceed 50%, at the lower temperature. The higher relative humidity can be permitted to be higher, but the max relative can not exceed 80%.
4.There is no dangerous medium or explosive or inflammable substance, gas or dust (include conductive dust) that can erode the metal and destroy the insulation exist in the installation place.
5. No drastic vibration is allowed in the installation place, the installation obliquity can’t exceed 5°.
6.Installation place should be far away from direct sunshine, rain or molds.

Technical data:
1.Rated current, capacity and surge-limiting times of mated capacitor.
2.Power frequency testing voltage: AC 50Hz, voltage 3Kv, no break-down or flash for 1min.
3.Temperature: Housing<=65K, Coil<=65K.

Model A B C R h a
12-16 Type 51 70 106 45 92 32
18-25 Type 55 74 118 45 99 43
25-40 Type 65 84 132 45 112 51

The specification for 6% reactance ratio

Model Rated Working
voltage (V)
Capacitor
Output(kvar)
Rated Working
Current (A)
 Inductance
(mH)
Current-limited
ratio (n)
Insulation level
(KV/1 min)
XD1-12 400 12 22.5 0.0315 50 2500
XD1-14 14 26.3 0.026
XD1-16 16 30.02 0.0232
XD1-20 20 35.9 0.0204
XD1-25 25 46.9 0.0213
XD1-30 30 56.3 0.025
XD1-40 40 70.8 0.03
Message Feedback

If you have any enquiry about quotation or cooperation,please free to email us at niki@zhiyue.com or use the following enquiry form,Our sales representative will contact you within 24 hous.thank you for your interest in our products.

News Center

Overview of high-voltage load switches, functions, precautions, environmental conditions, and application areas

What is high voltage disconnect switch?

Principles for the use of high-voltage isolation switches and circuit breakers

how to install high voltage power capacitor

Can't find what you're looking for?
In the past 32 years, Zhiyue Group Co., Ltd. has been helping many well-known companies and organizations to provide high-voltage power capacitors, low-voltage capacitors, vacuum contactors, vacuum circuit breakers, high-voltage load switches, high-voltage disconnect switch, high voltage transformer.
Contact Our Experts
Message
Cell Phones Telephone E-mail

Back To Top

Leave Message Here!
GET IN TOUCH NOW
×